Quick Answer
Bluebot includes two calibration tools to improve accuracy in specific situations: Set Zero Point (used to remove false or “noisy” flow readings) and K-Factor (used to align Bluebot’s totals with another known meter). Most users only need Set Zero Point, and many never need K-Factor at all.
Set Zero Point (Re-Zeroing)
What is Set Zero Point?
Set Zero Point recalibrates Bluebot’s baseline when no water is flowing. This is helpful if your device shows a very small flow reading even though all water is off.
This behavior—sometimes called false flow or signal noise—is a known and rare characteristic of transit-time ultrasonic flow meters. It does not mean your Bluebot is defective.
When should I use it?
Use Set Zero Point if:
You just completed installation and see irregular low flow
You moved Bluebot to a new water system
The app shows a small, steady flow (typically ~0.1–0.4 GPM) when no water is running
How to Set the Zero Point
Before starting, make sure no water is flowing. You may shut off the water temporarily if needed, but it’s not required if you’re confident there is no flow.
Open the Bluebot Water app
Start from the Dashboard
Tap the device showing false flow
Scroll to Hardware
Scroll to Calibration
Confirm no water is running
Tap Set Zero Point
Tap Yes to confirm
Wait a few seconds for calibration to complete
You’ll see a small positive or negative value appear. This is normal.
You can repeat Set Zero Point at any time if needed.
Important Warning
Do not run Set Zero Point while water is flowing
Doing so can temporarily make readings inaccurate
Only use this tool if you are sure the flow you see is false (usually very low)
Using Set Zero Point incorrectly can hide a real leak.
K-Factor Calibration
What is K-Factor?
K-Factor is an advanced calibration tool used to align Bluebot’s total usage with another known meter, such as:
A water utility meter
A mechanical master meter
A wellhead meter
This is commonly used in agricultural, commercial, or multi-meter systems.
When should I use K-Factor?
Use K-Factor only if:
You are comparing Bluebot to another verified meter
Both meters are measuring the same water over the same time period
You want long-term totals to match more closely
Most residential users do not need K-Factor.
Example
Utility or master meter shows 9,400 gallons
Bluebot shows 9,300 gallons for the same time period
K-Factor =
9,400 ÷ 9,300 = 1.0108
The app calculates this automatically for you.
How to Set the K-Factor
Write down:
Total gallons from the reference meter
Start and end dates for the measurement period
Open the Bluebot Water app
Start from the Dashboard
Tap your device
Open Settings
Scroll to Calibration
Tap Update K-Factor
Enter:
Bluebot gallons
Reference meter gallons
Period start and end dates
Save and wait for the update to complete
You may update the K-Factor at any time.
Important Warning
Do not set a K-Factor without verified data
Guessing or estimating values will cause inaccurate readings
K-Factor should not be used to correct short-term flow behavior
Which Calibration Tool Should I Use?
Seeing small flow when water is off? → Set Zero Point
Matching totals to another meter over time? → K-Factor
Not sure? → Start with Set Zero Point or contact support
Still Need Help?
If calibration doesn’t resolve the issue or you’re unsure which tool to use, contact Bluebot Support and we’ll help you determine the next best step.